Magik 3036 is an UL Classified, low VOC, water-based, flexible fire-resistant coating for duct insulation. It is washable, tough, and abrasion-resistant, and acts as a lagging and lap adhesive for canvas and glass reinforcing cloth. With excellent flow properties, Magik 3036 provides smooth brushing characteristics for better coverage and uniformly coated surfaces. It can be used both indoors and outdoors, including in high humidity environments.

Product Type: Insulating Coating, Lagging Adhesive, Lap Adhesive, Waterborne Coating

Features: Abrasion Resistant, Anti-Bacterial, Excellent Toughness, Flame Resistant, Good Washability, Low Emissions, Low VOC, UL Flame Rated, UV Resistant, Water Resistant, Water-based

Application Area: Air Conditioners, Duct Liner, Equipment, HVAC Ducts, Pipes, Seals

Compatible Substrates & Surfaces: Canvas, Glass Cloth

Application Method: Brush, Spray

Technical Data Sheet
  • TypeDocument Name
View All Documents

Enhanced TDS

Identification & Functionality

Features & Benefits

Labeling Claims
Ready-to-Use Product Features
Product Features
  • Zero Flame spread and Smoke developed
  • Excellent Adhesion and High Strength
  • Washable and Water Resistant
  • Compatible with various insulation substrates
  • Non Toxic and Non Flammable
  • UV Resistant
  • Antibacterial
  • Doesn't get discolored with age

Applications & Uses

Markets
Applications
Application Area
Application Method
Compatible Substrates & Surfaces
Product Applications

MAGIK 30-36 is used for outdoors as well as indoors-thermal insulation material to adhere fire resistant lagging cloth over metal duct, equipment & pipe insulation. MAGIK 30-36 may be applied to the joints or edges of fibrous duct liner insulation to seal and prevent air erosion. Magik 30-36 provides a protective finish for insulation on air conditioning ducts and cold water piping when applied in 2 coats with reinforcing fabric embedded between coats.

Application Procedure

The surface should be structurally sound, clean, dry, leveled and free from dust, curing compounds, grease and other loose debris. Keep container closed when not in use.

Apply MAGIK 30-36 at 1 - 1.8 m2 / liter (subject to surface condition). It is very important to ensure that each coat of MAGIK 30-36 is totally cured before the next coat is applied. The dry film thickness will vary with fabric selected. Use clean paint brushes which are suitable for water based paints.

Apply with full brush and spread out evenly.

Properties

Flame Rating
Physical Form
Appearance
White Thixotropic Paste
Specifications
ValueUnitsTest Method / Conditions
Specific Gravity1.20 - 1.50kg/ltrASTM D 1475-98
Solid Content60 - 64%ASTM D 1644
Viscosity55000 - 75000 cPsASTM D 2196
Water Vapor Permeance (at .030 inch dry film thickness)0.4 – 1.2permsASTM F 1249
VOCmax. 1g/ltr-
Drying Time (Set to Touch)2 - 3hrsASTM D 1640
Drying Time (Dry Through)15 - 17hrsASTM D 1640
Service Temperature- 20 - 100°C-
Product Properties
  • VOC Content - Meets requirements for LEED IEQ 4.2, Low Emitting Materials, Paints & Coatings.
  • Coverage Range - Wet coverages shown below are for smooth non-porous surfaces. Porous or rough surfaces may require more litres to obtain required dry thickness. 1 - 1.8 m2 /ltr per coat to obtain wet film thickness of 1 - 0.5 mm per coat.

Regulatory & Compliance

Packaging & Availability

Regional Availability
  • Middle East
Packaging Information

5 USG Plastic Pail

Storage & Handling

Shelf Life
12 months
Storage Conditions
  • 12 months from date of manufacturing in original unopened containers.
  • Store product (10°C - 40°C) for maximum storage life. Higher temperatures reduce normal storage life..
  • Lower temperatures may cause increased viscosity of a temporary nature.
  • Rotate stock on a “first in-first out” basis.
  • Failure to comply with the recommended storage conditions may result in premature deterioration of the product or packaging.