Enhanced TDS
Identification & Functionality
- Product Type
- Technologies
- Product Families
Features & Benefits
- Labeling Claims
- Ready-to-Use Product Features
- Product Highlights
- STIC-FASTM Adhesive is formulated for use in duct liner machines, both air atomized spray and roll coater types. It has excellent hot peel strength and high humidity resistance. Once dry and cured, it has outstanding water resistance.
- STIC-FASTM Adhesive is water-based and non-flammable in the wet state. It meets the requirements of ASTM C916-85, Type II (ASC-A-7001, Type II). STIC-FASTM Adhesive meets NFPA 90A & 90B 25/50 requirements.
Applications & Uses
- Application Area
- Application Method
- Compatible Substrates & Surfaces
- Preparation and Application Information
Material Preparation
Stir well. DO NOT THIN. Apply only to clean, dry, oil-free surfaces. Keep container closed when not in use.Application
- Spray: Apply the Foster® STIC-FASTM adhesive to the metal surface uniformly at 300 – 500 sq. ft./gal. (7.4 – 12.3 m2 /l). While still wet, press the insulation into place, making sure that complete contact is made with applied adhesive.
- Average viscosity range: 1,000 – 2,000 cps. Before using for the first time, existing spray systems must be completely cleaned and free of the old adhesive and solvents. Corrosion resistant pumps and fittings are suggested.
The following equipment combinations are suggested:
Model Spraygun Fluid Nozzle Air Cap Fluid Pressure Atomization Pressure
Binks 2001 SS 68 68PB 25 – 30 psi 60 – 70 psi DeVilbiss JGA-510 E 777 25 psi 60 – 70 psi - Not recommended for airless spray application.
- Brush/Roller
- Use clean equipment suitable for water-based paints..
Clean Up
To clean up, use warm soapy water if still wet. When dry, use xylene (flammable) or chlorinated solvent (non-flammable).- Limitations
- Apply between 40ºF (4ºC) and 100ºF (38ºC), protect from freezing until dry.
- Always test plastic foam insulation for warpage when using a water-based adhesive.
- Not suggested for sealing vapor barrier jackets.
- Overhead applications may require mechanical fasteners.
Properties
- Physical Form
- Typical Properties
Value Units Test Method / Conditions Average Weight / U.S. Gallon 8.8 lbs. ASTM D1475 Average Non-Volatile (by Volume) 51.0 % ASTM D2369 Average Non-Volatile (by Weight) 52.0 % ASTM D2369 Coverage Range (Spray) approx. 300 - 500 sq. ft./gal. - Coverage Range (Brush/roller) 150 - 300 sq. ft./gal. - Bonding Time Range 0 - 10 Minutes - Service Temperature Limits (at coated surface) -20 to 200 °F Wet Flammability 93.0 °C - - Flame Characteristics
Value Units Test Method / Conditions Flame Spread ¹ 0 ASTM E84 Smoke Developed ¹ 0 ASTM E84 - Note
¹ - Tested at coverage rate of 300 sq. ft. per gal. Applied to 1/4 inch (6.4 mm) inorganic reinforced cement board. The flame spread may vary at different product thicknesses and/or when applied over other surfaces.
Regulatory & Compliance
- Certifications & Compliance
- Chemical Inventories
- Quality Standards
Storage & Handling
- Storage Condition
Store between 40ºF and 100ºF, protect from freezing until dry.