Foster® 32-16 Fiber-FAS™ Duct Sealant

1 of 92 products in this brand
Foster® 32-16 Fiber-FAS™ Duct Sealant is a fire-resistant, fibrated, water-based sealant designed for use in heating and air conditioning ducts. It serves as both an adhesive and sealant, creating a durable seal against air leakage. This versatile product can be used with or without a reinforcing membrane.

Product Type: Waterborne Sealant

Compatible Substrates & Surfaces: Aluminum, Galvanized Steel, Metal

Application Method: Brush, Trowel

Features: Fire-Resistant, Flexible, Good Toughness, Water-based

Enhanced TDS

Identification & Functionality

Features & Benefits

Ready-to-Use Product Features
Product Highlights
  • Fiber-FAS™ Duct Sealant may be pressure tested within 16 hours dry time above 70°F (21°C) and below 60% RH. It quickly forms a strong bond to galvanized, aluminum or mild steel metal ducts. It has a mild odor when wet.
  • Fiber-FAS™ Duct Sealant will meet all SMACNA pressure classes up to 10" w.g. and SMACNA seal classes A, B and C on ducts constructed to SMACNA standards.
  • Fiber-FAS™ Duct Sealant contributes to USGBC LEED credits for SCAQMD Rule 1168 Compliance and Ozone Transport Commission (OTC) Compliance.

Applications & Uses

Application Method
Compatible Substrates & Surfaces
Preparation and Application Information

Material Preparation

DO NOT THIN. Apply only to clean, dry, oil-free surfaces. Keep container closed when not in use.

Application

UL 181B MASTIC CLOSURE OF UL 181 FLEXIBLE AIR DUCTS: Apply to clean, dry, oil-free surfaces by brush, trowel, or power extrusion. Uniformly brush out a 2” wide coat over the joint, at the nominal rate of 2 gal./100 sq. ft. (0.8 l/m2). Total coverage rate to be 45 – 55 sq. ft./gal. (1.1 – 1.4 m2 /l). Allow the completed joint to dry at least 24 hours above 70°F (21°C) before pressure testing. High humidities (over 70%) and/or cooler temperatures may retard drying. Total wet film thickness to be 32 mils +/- 3 mils.

Other Sealing Applications

Apply a continuous film of FOSTER® Fiber-FAS™ Duct Sealant over all areas of the indoor or outdoor duct system where air leakage may occur. A brush may be used to work the sealant into joints and remove excess. On spiral ducts, apply a coat to the male end of the coupling prior to fitting the straight run of spiral duct over it. Brush excess sealant over the joint to complete the seal. Screw holes and flanges should also be sealed with a coat of Fiber-FAS™ Duct Sealant. It may be applied to the inside or outside of the duct.

Power Extrusion

Fiber-FAS™ Duct Sealant may be applied using a wide variety of power (pressure) extrusion equipment suitable for use with water-based sealants. It is a soft buttery gel with a typical viscosity range of 130,000 - 160,000 cps. Corrosion resistant pumps are fittings are suggested.

Top Coating
After it is completely dry, Fiber-FAS™ Duct Sealant may be top coated with good quality water-based paint.

Clean Up

Use fresh water to clean brushes and equipment before product dries. Dry product may be removed with hot soapy water or strong solvent such as chlorinated solvent (non-flammable) or xylol (flammable).

 

Limitations
  • Always test foil and paper facings for acceptable adhesion. Outdoor horizontal surfaces must always drain completely.
  • A pitch of at least 1/2 inch per foot (4 cm/m) is required. If used between impermeable surfaces, drying time will be extended.
  • Mechanical fasteners of the type and number normally used for duct assemblies are required to provide rigidity to the duct system.

Properties

Color (Properties)
Physical Form
Typical Properties
ValueUnitsTest Method / Conditions
Average Weight / U.S. Gallon11.6lb/galASTM D1475
Average Non-Volatile (by Volume)55.0% ASTM D2369
Coverage Range (Brush, for 1.6 mm – 0.8 mm, wet film thickness)25 - 50sq. ft./gal.
Coverage Range (Caulking Gun, Linear, 1/8 in. bead)125.0ft./10.5 fluid oz. tube
Drying Time (Set to Touch)1.0Hour-
Drying Time (Dry Through)24.0Hours-
Shore Hardness (Type A)80.0-ASTM D2240
Wet Flammability99.0°C-
Water Vapor Permeance (at 35 mils, dry thickness)0.45permsASTM E96, Procedure A
Application Properties
ValueUnitsTest Method / Conditions
Service Temperature Range-7 to 93°C-
Flame Characteristics
ValueUnitsTest Method / Conditions
Surface Flame Spread¹5.0ASTM E84
Smoke Developed¹0.0ASTM E84
Note

¹ - Tested as applied in two 2 in. wide strips spaced 8 in. on center at a coverage rate of 25 sq. ft./gal. Applied to 1/4 inch (6.4 mm) inorganic reinforced cement board. The flame spread may vary at different product thicknesses and/or when applied over other surfaces.

Regulatory & Compliance

Storage & Handling

Handling Conditions
  • Store and apply between 40ºF (4ºC) and 100ºF (38ºC), protect from freezing until dry.
  • To resist rain washoff, allow at least 16 hours drying time above 40ºF (4ºC), with a relative humidity of 50%.
  • Higher humidity or lower temperatures may retard drying.