Foster® Air-Tight™ FDS-181 Duct Sealant

1 of 92 products in this brand
Foster® Air-Tight™ FDS-181 Duct Sealant is a fire-resistant, fibrate, water-based sealant designed for use on indoor or outdoor low, medium, and high-velocity heating and air conditioning ducts. It serves as a robust and flexible adhesive and sealant, creating a durable seal to prevent air leakage on the faced duct board, flex duct, galvanized aluminum, and stainless steel metal ducts.

Product Type: Waterborne Sealant

Application Area: AC Ducts, Air Ducts, All Service Jackets (ASJ), Board Facings, FRK Jackets, FSK Jackets, Joints, Lap Sealing

Compatible Substrates & Surfaces: Aluminum, Galvanized Steel, Metal, Steel

Application Method: Brush, Trowel

Features: Durable, Fire-Resistant, Flexible, Odorless, Water-based

Message our experts with questions
Robert Blackstone avatar

Robert Blackstone

Global Leader - Inside Sales

Please reach out to me with any questions, I am happy to assist you in finding the right product or learning more about our storefront

Enhanced TDS

Identification & Functionality

Features & Benefits

Ready-to-Use Product Features
Product Highlights
  • Air-Tight™ FDS-181 Duct Sealant is excellent for duct closure and butt joint seam sealing on both flexible and rigid faced fiberglass duct systems and sealing connections and penetrations in all metal ducts. It is non-flammable and has a mild odor when wet. It dries odor free.
  • Air-Tight™ FDS-181 Duct Sealant is ideal for vapor sealing ASJ, FRK and FSK jackets and board facings on rigid duct board at joints, laps and over staples and punctures.
  • Air-Tight™ FDS-181 Duct Sealant meets NFPA 90A and 90B 25/50 requirements.
  • Air-Tight™ FDS-181 Duct Sealant meets all SMACNA pressure classes up to 10” w.g. and SMACNA seal classes A, B and C on ducts constructed to SMACNA standards.
  • Air-Tight™ FDS-181 Duct Sealant has low VOC content and meets requirements of:
  • MAS Certified Green®
  • California Dept. of Public Health Standard Method v1.2
  • VOC Emissions and Content requirements to contribute to LEED v4 EQ Credit: Low Emitting Materials – Paints and Coatings
  • Collaborative for High Performance Schools EQ 7.1
  • SCAQMD Rule 1168

Applications & Uses

Markets
Applications
Application Area
Application Method
Compatible Substrates & Surfaces
Preparation and Application Information

Material Preparation

  • Do Not Thin.
  • Apply only to clean, dry, oil-free surfaces.
  • Keep container closed when not in use.

Application

  • UL 181A Mastic Closure of UL 181 Rigid Fiberglass Air Ducts: Apply to the surface by brush, trowel or power extrusion. Uniformly brush out at 3” – 4” wide tack coat over the stapled and smoothed joint at the nominal rate of 1.12 gal./100 sq. ft. (0.46 l/m2). Embed the reinforcing membrane into the tack coat, taking care that all of the mesh is filled. Pull the membrane taut and apply a second coat at the nominal rate of 1.12 gal./100 sq. ft. (0.46 l/m2). Allow the completed joint to dry at least 24 hours above 70°F (21°C) before pressure testing. High humidities (over 70%) and/or cooler temperatures may retard drying. Total (mastic plus scrim plus mastic) wet film thickness to be 36 mils. Fiberglass scrim to be 5 mils thick, 20x10 plain weave weighing 1.75 oz/yd2 (59 g/m2).
  • UL 181B Mastic Closure of UL 181 Flexible Air Ducts: Apply to clean, dry, oil-free surface by brush, trowel or power extrusion. Uniformly brush out at 2” wide coat over the joint at the nominal rate of 1.87 gal./100 sq. ft. (0.76 l/m2). Total coverage rate to be 53.5 sq. ft./gal. (1.31 m2/l). Allow the completed joint to dry at least 24 hours above 70°F (21°C) before pressure testing. High humidities (over 70%) and/or cooler temperatures may retard drying. Total wet film thickness to be 30 mils (0.76 mm).
  • Metal Duct Sealant : Apply at a rate of 50 – 55 sq. ft./gal. (1.23 – 1.35 m2/l). Work into crevices and ensure sealant film bridges all gaps maintaining minimum film thickness over seams. Reinforcing membrane is not required for sealing metal duct. Allow the completed joint to dry at least 24 hours above 70°F (21°C) before pressure testing.
  • Other Duct Closure Applications: For other applications sealing foil faced insulation boards and duct wrap the use of a reinforcing membrane may be optional and shall be used depending on the system design. Apply at a rate of 50 – 55 sq. ft./gal. (1.23 – 1.35 m2/l). Allow the completed joint to dry at least 24 hours above 70°F (21°C) before pressure testing.
  • High humidities (over 70%) and/or cooler temperatures may retard drying. For best results, do not exceed 1/8” (3.2 mm) wet film thickness. AIR-TIGHT™ Duct Sealant is weather, water and UV resistant, allowing it to be used outdoors and in high humidity environments.
  • Limitations: Always test foil and paper facings for acceptable adhesion before using. Outdoor horizontal surfaces must always drain completely. A pitch of at least 1/4” per foot (2 cm/m) is required. To resist rain washoff, allow at least 12 – 15 hours drying time above 40°F (4°C), with a relative humidity of 50%. Higher humidity or lower temperatures may retard drying.
  • Power Extrusion: AIR-TIGHT™ Duct Sealant may be applied using a wide variety of power (pressure) extrusion equipment suitable for use with water- based sealants. It is a soft buttery gel with a typical viscosity range of 130,000 – 150,000 cps. Corrosion resistant pumps and fittings are suggested.
Cleaning Information

Use fresh water to clean brushes and equipment before product dries. Dry product may be removed with hot soapy water or strong solvents such as chlorinated solvent (non-flammable) or mineral spirits (flammable).

Properties

Physical Form
Typical Properties
ValueUnitsTest Method / Conditions
Average Weight12.0lbs.ASTM D1475
Average Non-Volatile (by Weight)69.0% ASTM D2369
Coverage Range (Brush)45 - 55sq. ft./gal.-
Drying Time (Set to Touch)1.0Hours-
Drying Time (Dry Through)16.0Hours-
Wet Flammability99.0°C-
Application Properties
ValueUnitsTest Method / Conditions
Service Temperature Range-7 to 93°C-
Flame Characteristics
ValueUnitsTest Method / Conditions
Flame Spread ¹20ASTM E84
Smoke Developed ¹15ASTM E84
Note

Tested at coverage rate of 45 sq. ft. per gal. in a 3 in. (7.6 cm) strip. Applied to rigid fiberglass duct board. Type 475, covered with foil/scrim/kraft paper facing material.

Regulatory & Compliance

Storage & Handling

Shelf Life
12 months
Storage Information
  • Store and apply between 40°F (4°C) and 100°F (38°C), protect from freezing until dry.
  • Use of mesh reinforcement is required for applications meeting UL181A Closure systems