Enhanced TDS
Identification & Functionality
- Product Type
- Technologies
- Product Families
Features & Benefits
- Ready-to-Use Product Features
- Product Highlights
- DUCT-FAS® ADHESIVE has full coverage spray characteristics with conventional or airless spray equipment with little tendency to cobweb. Its high solids and gel-like consistency make it ideal for vertical or overhead surfaces and for brush or roller application.
- DUCT-FAS® ADHESIVE meets ASTM C916, Type IV (ASC- A-7001A, Type IV) and NFPA 90A and 90B 25/50 requirements. DUCT-FAS® ADHESIVE is produced under the classification and follow-up service of Underwriters Laboratories, Inc.
Applications & Uses
- Application Area
- Application Method
- Compatible Substrates & Surfaces
- Preparation and Application Information
Material Preparation
Stir well. DO NOT THIN. Apply only to clean, dry surfaces. Keep container closed when not in use to prevent solvent evaporation. If stored below 60°F, the product should be conditioned in its unopened container at room temperature for at least 24 hours before usage.Application
Clean all surfaces thoroughly. Make sure the surfaces are free of any oil residue. Spray apply a uniform coverage of adhesive to one surface at 300 – 500 sq. ft./gal. (7.4 – 12.3 m2 /l). While the adhesive is still w et, combine substrates w ith sufficient pressure to ensure 100% contact.Spray Equipment Suggestions
Model Spraygun Fluid Nozzle Air Cap Fluid Pressure Atomization Pressure
Binks 2001 SS 63BSS 63PB 15 – 20 psi 40 – 50 psi DeVilbiss JGA-510 E 777 15 – 20 psi 40 – 50 psi Clean Up
Use a chlorinated solvent (non-flammable) or xylol (flammable).- Limitations
- Always test plastic and painted materials for compatibility when using a solvent-based product.
- Allow to dry to a solvent-free condition before installing weld pins.
- Not suggested for sealing vapor barrier jackets.
- Overhead applications may require mechanical fasteners.
Properties
- Color (Properties)
- Typical Properties
Value Units Test Method / Conditions Average Weight / U.S. Gallon 6.5 lbs. ASTM D1475 Average Non-Volatile (by Volume) 20.0 % ASTM D2369 Average Non-Volatile (by Weight) 28.0 % ASTM D2369 Bonding Time Range 0 - 15 Minutes - Coverage Range ¹ 300 - 500 sq. ft./gal. Wet Flammability -7.0 °C - - Application Properties
Value Units Test Method / Conditions Service Temperature Limits (at coated surface) -20 to 200 °F - Flame Characteristics
Value Units Test Method / Conditions Flame Spread ² 8 ASTM E84 Smoke Developed ² 25 ASTM E84 - Note
¹ - Subject to type of surface and nature of material being bonded. 0.005 in. - 0.003 in. wet film thickness.
² - Tested at coverage rate of 200 sq. ft./gal. Applied to 1/4 inch (6.4 mm) inorganic reinforced cement board. The flame spread may vary at different product thicknesses and/or when applied over other surfaces.
Regulatory & Compliance
- Certifications & Compliance
- Chemical Inventories
Storage & Handling
- Storage Condition
Store and apply between 40°F and 100°F